Honeywell CC-PAIH01 HART High Level Analog Input Module
Manufacturer: Honeywell Process Solutions
Model: CC-PAIH01 (P/N:51405038-175)
Series: Experion PKS C300 Series C I/O System
Type: 16-Channel HART High Level Analog Input Module
Function: Collect 4-20mA / voltage process signals, bidirectional HART 7 communication for smart transmitter configuration, diagnostics and secondary variable reading
1. Overview
CC-PAIH01 is a high-density HART analog input module for Honeywell Experion PKS C300 DCS. It supports 16 configurable analog channels (12 single-ended / 4 differential) to acquire 4-20mA current and voltage signals from pressure, flow, level and temperature transmitters. Built-in HART 7 protocol enables simultaneous analog measurement and digital two-way communication with smart field instruments, supporting remote calibration, wire break detection, device fault diagnosis and multi-variable acquisition. It matches CC-TAIX01 non-redundant / CC-TAIX11 redundant IOTA terminal bases, adopts G3 conformal coating and hot-swap design for reliable operation in critical process industries.
2. Technical Specifications
• Power Supply: 24 VDC ±10%, typical consumption 4.5W
• Channel Configuration: 12 single-ended / 4 differential, total 16 channels
• Supported Signals: 4–20mA, 0–5V, 1–5V, 0–10V DC
• ADC Resolution: 16-bit high precision conversion
• Measurement Accuracy: ±0.05% FS at ambient temperature, ±0.15% FS full temperature range
• HART Standard: HART 7, point-to-point & multi-drop mode
• Isolation: 1500V channel-to-channel isolation, strong EMI suppression
• Operating Temperature: -40°C ~ +70°C
• Storage Temperature: -40°C ~ +85°C
• Humidity: 5%~95% RH non-condensing
• Dimensions: 142 mm × 82 mm × 54 mm
• Weight: Approx. 0.35 kg
• Coating: G3 conformal coating for corrosive environments
• Feature: Hot-swappable, compatible with redundant C300 controller system
• Certifications: CE, UL, CSA, SIL2 compliant
3. Key Features
• Integrated HART 7 Communication: Dual signal transmission of analog process value and digital device diagnostic data
• 16 High-Density Channels: Mixed single-ended/differential wiring to eliminate ground loop interference
• Comprehensive Channel Diagnostics: Wire break, over-range, short-circuit and transmitter fault alarm
• High Noise Immunity: 120dB CMRR at 50/60Hz, channel isolation anti-interference design
• Hot-Swap Online Replacement: Module change without controller shutdown
• G3 Conformal Coating: Adapt to damp, dusty and corrosive plant environments
• Redundant System Support: Matches redundant IOTA bases for high-availability control loops
4. Applications
• Thermal & Combined Cycle Power Plant DCS Process Measurement
• Refinery, Petrochemical & Chemical Plant Flow/Pressure/Temperature Monitoring
• Oil & Gas Pipeline, Compressor Station Instrument Data Acquisition
• Water Treatment, Pharmaceutical and Metallurgical Continuous Process Control
Honeywell © CC-PAIH01 HART High Level Analog Input Module